Texas Journeyman Electrician Practice Test
Timed on the two Texas portion clocks, 132 seconds a knowledge item and 254 a calculation, then scored by content area along with the three items that ate your clock.
Before you start
Open your code book first. Every answer here can be found in it, and finding it fast is the skill the exam room tests.
Any table value a question needs is given to you in the stem. You are scored on the method, and that is where marks are won or lost.
Exam simulation follows the published blueprint, about 7 knowledge questions for every 3 calculations, on the real per-portion clock. Answers stay hidden until you submit, the same as in the room, and a review screen comes first. Practice tilts toward calculations on purpose, since those portions have the lower pass rates, and explains each question as soon as you answer it.
The Texas journeyman exam these questions follow
TDLR licenses Texas electricians, and PSI gives the exams for it. The journeyman exam is two portions in one sitting, NEC knowledge and calculations, each scored on its own. You book with PSI, and the $78 fee covers both portions. The journeyman exam page has the outline by subject area and the retake rules.
The two portions and their clocks
The knowledge portion is 59 items in 130 minutes, 56 of them scored, and the calculations portion is 26 items in 110 minutes, 24 of them scored. Each portion passes at 70 percent, so a candidate who passes one and fails the other rebooks only the portion they lost. For fiscal year 2025 TDLR reported 20.56 percent passing journeyman calculations and 24.46 percent passing journeyman NEC knowledge. The exam simulation here keeps both paces, 132 seconds for a knowledge item and 254 for a calculation.
The one book in the room
The reference list is the National Electrical Code and nothing else, and every sitting since 1 September 2026 has been referenced to the 2026 edition. The book has to be soft-bound, the handbook edition stays home, and the only tabs allowed are ones the code publisher made or supplied. You can highlight and write notes in the book before the session, and the bulletin bars marking it during the session. Bring a plain, non-programmable calculator, and answer by the standard method, because the bulletin tells you to leave code exceptions and optional calculations alone unless a question asks for them.
Ten free questions, worked
The blueprint gives calculations 24 of the 80 scored items, and six of the 20 in the timed run above are calculations, the same share. Across all 30 the calculations run from three-phase apparent power and a motor nameplate checked against the table to bends between pull points, a terminal block in a box and conductors upsized in a nearly full raceway. The code questions take in the 2026 adoption date, a system bonding jumper at a transformer, pool bonding, a detached shop on a feeder, informational notes and the reach of an exception. The first ten are printed below with their answers.
When does Texas adopt the 2026 National Electrical Code?
- When each municipality chooses
- It has not adopted it
- January 1, 2026
- September 1, 2026
Answer: D. The adoption is effective September 1, 2026. Local amendments can still modify it within a jurisdiction.
A three-phase load draws 30 amperes at 480 volts. What is the apparent power?
- 24.9 kilovolt-amperes
- 14.4 kilovolt-amperes
- 43.2 kilovolt-amperes
- 8.3 kilovolt-amperes
Answer: A. Three-phase apparent power is voltage times current times the square root of three. 480 times 30 is 14,400, times 1.732 is about 24,900 volt-amperes.
An installer puts a system bonding jumper at a transformer and a second one at the first disconnecting means downstream, calling it redundancy. What is the result?
- No effect at all, since the second jumper carries no current
- A correct installation, since either location is permitted
- A correct installation, since the two jumpers are in parallel
- Neutral current on the metal between the two bonding points
Answer: D. 250.30(A)(1) permits the system bonding jumper at the source or at the first disconnecting means, and at one of those places only.
A run between two pull points already contains 315 degrees of bend, and the installation needs one more 90 degree bend before the run ends. What does the code require?
- Nothing, since no single bend exceeds 90 degrees
- A larger bending radius on the added bend
- The next trade size up, to reduce pulling tension
- A pull point, since the run would otherwise reach 405 degrees
Answer: D. 315 plus 90 is 405 degrees, and the limit between pull points is 360. The fix is to install a box or a conduit body so the run ends before the added bend and a new run begins after it, and the count then starts again from zero.
The equipotential bonding around a permanently installed pool is often described as grounding the pool. What is it actually doing?
- Lowering the resistance of the grounding electrode system
- Standing in for the equipment grounding conductor of the pool equipment
- Carrying fault current back to the service
- Holding the water, the deck and the metal parts near the pool at the same potential
Answer: D. A person in a pool bridges two points. If those points sit at different voltages, current runs through the person with nothing faulted and no overcurrent device that will ever see it.
A motor nameplate reads 26 amperes. The full-load current table for that horsepower and voltage gives 28 amperes. Which value sizes the branch-circuit conductors?
- 26 amperes, the nameplate value
- The average of the two
- Whichever is larger
- 28 amperes, the table value
Answer: D. Conductors, switches and short-circuit protection come from the table. The nameplate is used for overload protection and essentially nothing else in this calculation.
A detached shop is fed by a feeder with an equipment grounding conductor, and a grounding electrode system is installed at the shop. Where do those two conductors land in the shop panel?
- Feeder grounding conductor on the neutral bar, electrode conductor on the ground bar
- Both on the equipment grounding bar, with the neutral bar isolated
- Electrode conductor on the neutral bar, feeder conductor on the ground bar
- Both on the neutral bar, which is bonded to the enclosure there
Answer: B. 250.32(B) runs an equipment grounding conductor with the feeder and connects it to the disconnecting means at the structure, and 250.32(A) puts an electrode system there whose conductor lands in the same place.
A pull uses 78 percent of the permitted conductor area. Every conductor is replaced with the next size up, whose area is 1.27 times as large, and the count stays the same. Does the pull still fit?
- Yes, at about 61 percent of the permitted area
- No, at about 105 percent of the permitted area
- Yes, at about 99 percent of the permitted area
- No, since increasing a conductor size always requires the next trade size
Answer: C. Since every conductor grows by the same ratio, the total grows by that ratio too. 78 percent times 1.27 is 99.1 percent, so the pull still fits, with very little to spare.
An exception is printed under a section. What does it modify?
- The rule it is printed under, and nothing else
- Every section in that part of the article
- Only installations the authority having jurisdiction agrees to
- The scope of the article
Answer: A. An exception belongs to the rule directly above it and modifies that rule alone. Where a section carries several, they are numbered and each still reaches only that section.
A box question lists a terminal block among its contents. What allowance does it add?
- Two, the same double allowance a device yoke gets
- One for each terminal on the block
- One, based on the largest conductor landed on it
- None, because a terminal block is not a device
Answer: C. Terminal block fill is its own category and each assembly takes a single allowance, based on the largest conductor terminated to that assembly.
The timed run above uses questions 11 to 30.
Trojan Digital Marketing wrote these questions for its electrician exam sites, and most of them appear in its other state banks too. None came off a real exam, and no NEC table or text appears anywhere on the site. Texas Electrician Exam is independent study material from Trojan Digital Marketing. It has no tie to NFPA, TDLR, PSI Services or any licensing authority, and none of them endorses or sponsors it. NEC and National Electrical Code are registered trademarks of the National Fire Protection Association. Check every rule against your own code book, and take questions about real work to your inspector.