Texas Electrician ExamJourneyman and master exam prep Free timed testFree test

Checked against primary sources 2026-08-24

NEC 240.6(D) Remote Operated Breakers: Older Than You Think

The networked breaker rule arrived in the 2023 edition. A breaker whose rating can be raised from somewhere else is a breaker whose protection can be removed from somewhere else, and the code has said so since the 2023 edition.

Quiz yourself: did this section move?

On this page
  1. What the section covers
  2. The two conditions
  3. Which edition this is actually in
  4. The standards it points at, and where they sit
  5. What it changes on a job
  6. Questions people ask
  7. What this page cites

What the section covers

A circuit breaker whose trip setting can be adjusted remotely gets to be treated as rated at its adjusted setting only when access to that adjustment is controlled at both ends (NEC 240.6(D)).

Adjustable-trip breakers are not new. What changed is that a lot of them now sit on a network, so the setting that decides how much current the circuit is protected at can be moved by somebody who is not standing in front of the panel.

The code treats that as an overcurrent protection question, because it is one. If the adjustment is reachable and unguarded, the rating you designed to is not the rating the installation actually has.

The two conditions

Local restricted access comes first, and it uses the methods already in 240.6(C): behind a sealable cover over the adjusting means, behind a bolted equipment door, behind a locked door available only to qualified personnel, or password protected with the password held by qualified personnel.

Remote access is the second half. It is satisfied by a local nonnetworked interface, or by a networked interface that meets one of two tests.

That second option is the one with teeth on a live job, because it produces a document somebody has to be able to hand over.

Which edition this is actually in

The 2023 edition. 240.6(D) is one of a small group of sections that brought cybersecurity language into NFPA 70 in that cycle, alongside 110.3(A)(8) on examining network-connected equipment and 708.7 in the critical operations power systems article.

The number held in the 2026 cycle. If your tab points at 240.6 it still lands in the right place. The printed 2026 book does put a delta beside 240.6(D), NFPA's mark for words deleted within a section, so read the subsection in your new copy before you quote it from the old one.

That matters mainly because the section keeps being described as a 2026 arrival, including once on this site. It is worth knowing which of the things you are being told are new actually are.

The standards it points at, and where they sit

ISA 62443, UL 2900 and NEMA CY70001 appear only in informational notes attached to the section. The code treats an informational note as explanatory material that sets no requirement (NEC 90.5(C)).

So an inspector cannot cite you for failing to follow ISA 62443. What is enforceable is the sentence in 240.6(D) itself: the evaluation, or the completed risk assessment with its documentation. The named standards tell you what a defensible answer looks like.

None of those are electrical standards, which is the genuinely interesting part. The code reached outside its own discipline because the failure mode it is worried about is not electrical either.

What it changes on a job

The answer to "can we put this breaker on the building network" used to be an IT decision made after the electrical design was finished.

It now has a code section attached to it, and the documentation route means somebody has to be able to produce a risk assessment when asked. On an industrial or institutional job with networked protection, that is a deliverable, and deciding who owns it late is expensive.

The practical read for a working electrician: if the adjustment is only reachable from a local, nonnetworked interface, you are in familiar territory and 240.6(C) is the whole job. The moment it is on a network, somebody has to hold a document.

Questions people ask

Is remote access to an adjustable trip circuit breaker permitted?

Yes, on conditions. A breaker whose trip setting can be adjusted remotely is permitted to be treated as rated at that adjusted setting only where local access to the adjusting means is restricted by one of the four methods in 240.6(C), and remote access is either through a local nonnetworked interface or through a networked interface that meets one of two tests (NEC 240.6(D)).

What documentation does 240.6(D) ask for?

One of the two networked routes is the documented one. It asks that a cybersecurity risk assessment of the network has been completed, with the documentation and certification available to those authorized to inspect, operate and maintain the system. The other route asks instead that the breaker and the program used to adjust it be identified as having been evaluated for cybersecurity. The standards named alongside sit in informational notes, which the code treats as explanatory and unenforceable (NEC 90.5(C)).

When did the 240.6(D) rule arrive?

In the 2023 edition. It is one of a small group of sections that brought cybersecurity language into NFPA 70 that cycle, alongside 110.3(A) on examining equipment and the critical operations power systems article. If you are holding a 2023 book, the section is already in it.

What changed in 2026?

Nothing that changes the answer. The 2026 book marks 240.6(D) with a delta for deleted words, and the 2026 section still turns on the same two conditions. The number did not move either, so a tab at 240.6 still lands where you left it.

Does 240.6(D) apply to dwelling panels?

The section is written about adjustable-trip circuit breakers and says nothing about occupancies, so nothing in it carves out a dwelling. In practice the equipment it describes sits on industrial and institutional jobs with networked protection, which is where the documentation becomes a deliverable somebody owns. Read the section itself before reasoning from where you usually meet the hardware.

Before the exam, or the inspection

See where 50 of the 2023 numbers went

Fifty 2023 numbers, each with where the rule sits now, what took over the old number, and the document it was read in. $29 once, and ten of them are free in the quiz first.

37 of the 50 were read in the printed 2026 book, 12 in NFPA panel drafts, and 1 is not settled. Each row says which, and corrections go in the public log.

What this page cites

An email when a Texas exam rule or fee changes

TDLR writes Texas exam rules and fees into 16 TAC Chapter 73, which also sets the code edition, and PSI's candidate bulletin carries the exam details. If either changes an exam rule, a fee or a code date, we send one short email about it, and the link at the bottom of every email takes you off the list.