Texas Electrician ExamTexas journeyman & master

Box fill, and the six things that get counted differently

Short section, heavily tested, and almost every wrong answer comes from miscounting rather than from bad arithmetic.

On this page
  1. The shape of the problem
  2. The six categories, and what makes each one a trap
  3. The grounding conductor count, which is where most people are working from an old rule
  4. Everything is sized by the largest conductor, not its own size
  5. What does not count at all
  6. Finding the box volume
  7. The method
  8. What this page cites

The shape of the problem

Box fill is a counting exercise before it is ever an arithmetic one, and the grounding conductor count is not what most people remember Each conductor that originates outside the box and terminates or is spliced inside counts once, and so does each conductor that passes through without splice or termination. Up to four equipment grounding conductors together take one volume allowance, and each one beyond four takes a quarter allowance. All internal cable clamps together take one. Each yoke or strap holding a device takes a double allowance. Each terminal block assembly takes one. Small fittings such as locknuts and bushings take nothing. The counts are then multiplied by the volume for the wire size, which is in the code book. device box, cut away each conductor that terminates inside, or passes straight through 1 each equipment grounding conductors, up to four of them together 1 total every one after the fourth ¼ each all internal cable clamps 1 total each yoke or strap with a device 2 each each terminal block assembly 1 each locknuts, bushings, small fittings 0 count × the volume for that wire size the volume comes out of your book, not off this page the quarter allowance is the one people miss
Get the count right and the arithmetic is trivial. Almost every miss is a count, not a multiply. Drawn against NEC 314.16(B)(1) through (B)(6). Volumes are in Table 314.16(B)(4), in your book.

A box fill question gives you a box and a list of what is inside it. It wants to know whether the box is big enough, or which box you need.

Underneath it is one comparison: the volume required by everything in the box against the volume the box provides. The arithmetic is addition. The difficulty is deciding what counts and how much each thing counts as.

The code sets that out in six categories, and they do not all work the same way (NEC 314.16). Getting the categories right is the entire skill.

The six categories, and what makes each one a trap

Read that list again and notice the pattern. Some categories count per item. Some count the whole group as one. That split is where the points go.

The grounding conductor count, which is where most people are working from an old rule

The rule people carry in their heads is that every equipment grounding conductor in the box, however many there are, adds up to a single allowance. That was true for a long time. It is not what 314.16(B)(5) says now.

What it says now: up to four grounding conductors take one allowance between them. Each one after the fourth takes a quarter allowance. Both are sized on the largest grounding conductor entering the box.

So six grounding conductors are not six allowances, and they are not one either. They are one and a half. A candidate counting six has invented volume that does not exist. A candidate counting one has lost half an allowance, which is the more dangerous direction because it selects a box that is too small.

Clamps genuinely do work the old way, and get miscounted the same way. Three internal clamps is one allowance, not three.

Everything is sized by the largest conductor, not its own size

This catches people who understand the categories perfectly.

When you allow volume for a device, a clamp, a support fitting or the grounding group, you use the volume of the largest conductor connected to that item, not the size of the item and not the average.

So a box with 12 AWG circuit conductors and a 14 AWG grounding conductor allows for the grounding conductors at the 14 AWG volume, because that is the largest grounding conductor entering the box. But a device fed by the 12 AWG gets the 12 AWG volume, twice.

Two different largests in the same box. Read which group each item belongs to.

What does not count at all

Small fittings get no allowance. Locknuts, splicing connectors and bushings are specifically excluded (NEC 314.16(B)).

That is worth knowing because a question will list wire nuts in the inventory. They are there to be ignored.

Pigtails made up entirely inside the box also do not count, because they never originate outside it.

Finding the box volume

The volume of a box is the total of the assembled sections, plus anything marked with its own volume: plaster rings, domed covers, extension rings.

That last part is the giveaway on questions that look impossible. A box that is too small becomes large enough once the marked plaster ring is added, and the question includes the ring specifically to see whether you add it.

Boxes at or below 100 cubic inches that are not in the standard table, and all nonmetallic boxes, are marked by the manufacturer with their volume (NEC 314.16(A)). If a question gives you a marked volume, use it and do not go to the table.

The method

  1. Inventory what is in the box and sort it into the six categories.
  2. Identify the largest conductor in the box, and separately the largest in each group that is sized off a group.
  3. Total the allowances, remembering that clamps and the grounding group are one each regardless of quantity.
  4. Find the box volume, adding any marked rings or covers.
  5. Compare. If required exceeds provided, go up a size.

Do the sorting on paper before touching a table. Almost every error in this section happens in step one, and no amount of care in steps three and four fixes it.

What this page cites

NEC and National Electrical Code are registered trademarks of the National Fire Protection Association.

Trojan Digital Marketing is an independent company. We are not affiliated with, endorsed by, or sponsored by NFPA, TDLR, PSI Services, or any licensing authority.

Bring your own current copy of the National Electrical Code. The Texas exam is open book.

All practice questions are original. They are not actual exam questions.

Built and maintained by Jeff Clerisier, Trojan Digital Marketing.