Texas Electrician ExamTexas journeyman & master

The grounding electrode conductor, and the caps most people miss

Sizing straight off the table gives the wrong answer on any rod-only or concrete-encased system. Three short subsections cap it, and they are where the question lives.

On this page
  1. The table is the starting point, not the answer
  2. The three ceilings
  3. The condition attached to all three
  4. Why a rod gets a ceiling at all
  5. Installation rules that get tested alongside sizing
  6. The aluminum rules pull in opposite directions
  7. A separate table you will also be asked about
  8. What this page cites

The table is the starting point, not the answer

The grounding electrode conductor is sized from a table indexed by the size of the largest ungrounded service conductor (NEC 250.66).

Find your service conductor size in the left column, read across, take the value. That is the method, and on a question with a water pipe electrode it is the whole method.

But the section that sends you to the table also says except as permitted in the three subsections that follow it. Those three subsections cap the result, and which one applies depends entirely on what kind of electrode is at the other end.

The three ceilings

Each one names a maximum, above which a larger conductor is not required (NEC 250.66).

These are not small adjustments. On a large service the table can call for a conductor several sizes above the ceiling. A candidate who reads the table and stops will confidently answer with a conductor two or three trade sizes too big.

The condition attached to all three

Every one of the three ceilings carries the same qualifier, and it is the part that gets skipped: the ceiling applies only where that conductor does not continue on to another type of electrode that requires a larger conductor.

So a conductor running to a ground rod and stopping is capped. The same conductor running to a ground rod and then continuing to a water pipe is not, because it is now serving an electrode that has no ceiling.

Exam questions test this by describing a grounding electrode system with more than one electrode in it. The presence of a second electrode type is the tell.

Why a rod gets a ceiling at all

It is worth understanding rather than memorizing, because the reasoning is the same one from the bonding article.

A driven rod has high resistance to earth, tens of ohms in ordinary soil. The current that can flow through it is limited by that resistance, not by the conductor feeding it. Past a certain point, a larger conductor to the rod accomplishes nothing at all.

A concrete-encased electrode has lower resistance than a rod, which is why its ceiling sits one size larger. A metal water pipe has lower resistance still, which is why it gets no ceiling.

The ceilings track how much current the electrode can actually pass. Once you see that, remembering which electrode gets which cap stops being arbitrary.

Installation rules that get tested alongside sizing

A few short rules from the installation section come up often enough to know.

That last one surprises people. A steel sleeve protecting a grounding electrode conductor makes things worse unless it is bonded, because the changing magnetic field induces an opposing current in the steel.

The aluminum rules pull in opposite directions

If the conductor is aluminum or copper-clad aluminum, two distance rules apply and they measure from different surfaces (NEC 250.64(A)).

One permits a termination within 18 inches of the bottom of an outdoor enclosure that is listed and identified for the environment. The other forbids terminating within 18 inches of the earth.

Same number, opposite direction, and a question can quote either one. Read which surface is being measured from before you answer.

Aluminum also cannot be in direct contact with concrete, or installed where conditions are corrosive, unless it has an extruded polymeric covering.

A separate table you will also be asked about

The grounding electrode conductor is not the equipment grounding conductor, and they are sized from different tables.

The grounding electrode conductor runs from the service to the earth electrode, sized by service conductor size. The equipment grounding conductor runs with the circuit conductors, sized by the rating of the overcurrent device ahead of it.

Reaching for the wrong table is a common error because both are in Article 250 and both produce a conductor size. Ask what the conductor connects to. If it terminates on an electrode, it is the grounding electrode conductor.

What this page cites

NEC and National Electrical Code are registered trademarks of the National Fire Protection Association.

Trojan Digital Marketing is an independent company. We are not affiliated with, endorsed by, or sponsored by NFPA, TDLR, PSI Services, or any licensing authority.

Bring your own current copy of the National Electrical Code. The Texas exam is open book.

All practice questions are original. They are not actual exam questions.

Built and maintained by Jeff Clerisier, Trojan Digital Marketing.