Checked against primary sources 2026-09-18
Motor and transformer circuits on the Texas journeyman exam
Motors carry two of the twenty-four scored calculation items on the journeyman paper. The reputation they have for dominating the math belongs to the master exam, where it is six of thirty.
Test yourself: thirty free questions, twenty of them timed
On this page
What motors are actually worth here
The published content outline gives motors and generators two of the twenty-four scored items on the journeyman calculations portion, and five of the fifty-six on the knowledge portion. On the master calculations portion it is six of thirty, and services is eight. That is where the idea that motors dominate the calculations comes from, and it is true one license class up from this one.
Our bank holds forty-three questions in this area, with a difficulty spread of two, twelve, twenty and nine across the four bands. Sixty-one of the five hundred mention a motor somewhere, across six different subject areas, which is the more useful number: motor language shows up inside questions that are filed under conductors, grounding and installations.
Motor items turn up on both portions, and the journeyman exam page sets out how each portion is timed and scored.
The rule the whole area turns on
Table current sizes the conductor, nameplate current sets the overload
430.6 sends you to the table for conductor sizing and to the nameplate for overload protection. Six questions in this area hand you both currents in the same stem, and the wrong answer is always the one that used the other number.
The motor calculations page works that split, and overload protection covers what the nameplate current does once you have it. Read them in that order.
The six topics
- Motor calculations on the Texas journeyman exam, and the split that decides most of the points. 430.6 sends you to a table for one current and to the nameplate for another.
- Feeders for a group of motors, and the allowance candidates hand out more than once. Largest motor at 125 percent, the rest at full load, in that order.
- Overload protection, fault protection and the disconnect, and why the exam keeps them apart. 430.32 by service factor and temperature rise, with the nameplate current.
- HVAC circuits on a Texas paper, where a national answer and a Texas answer come apart. Article 440 plus the Texas 210.8(F) amendment the national text retires.
- Transformer questions on a Texas paper, and the number that moved under everybody. Primary and secondary protection under 450.5, moved from 450.3 in 2026.
- Elevators and escalators on a Texas paper, and the trade the licensing act leaves alone. Article 620 on the paper and Tex. Occ. Code 1305.003 on the job.
Where the area gets hard
Eleven of the forty-three mention a feeder, and five of the nine hardest questions in this area are feeder problems. The rule is simple to state and easy to execute backwards: the largest motor at 125 percent, every other motor at its full load current, added together. Candidates who apply 125 percent to all of them, or to none, land on numbers that are offered as answer choices. Motor feeder sizing is the page for it.
The Texas amendment that outlives the national rule
The national 2026 text carries an exception at 210.8(F) for listed outdoor HVAC equipment with a sentence that expired it on 1 September 2026. 16 TAC 73.100(b) adopts that exception with the expiry sentence removed. So the exception the rest of the country lost on that date is the one Texas kept, and the code you are examined on is the code as Texas adopted it.
The HVAC page prints the whole thing, both sides. It is the clearest case on this site of why the adopted state edition and the national edition are worth keeping separate in your head.
What these cost on the job
A motor circuit sized from the nameplate current where the table current was called for produces a conductor that passes a visual check and fails a load. The overload set from a table current where the nameplate was called for protects the wrong thing. Both errors survive the install and surface under running load, which is the expensive place to find them.
The HVAC side carries a live Texas difference that matters on a permit as much as on a paper, since the exception Texas keeps is one the national text retires on the same date. The HVAC page prints both.
Where motor language shows up elsewhere
Sixty-one of the five hundred questions mention a motor and they sit in six different subject areas. A conductor sizing item can carry a motor load. A grounding item can turn on the equipment grounding conductor for a motor circuit. A disconnect item can be a motor disconnect with the fifty foot half of in sight from attached to it. The published two calculation items are a poor guide to how often the vocabulary appears.
That is the argument for reading this area even at its light published weight: the method transfers. Conductor sizing and disconnecting means both collect motor-flavored items.
What to do with this before test day
Tab 430.6, 430.24, 430.32, 440 and 450.5. Then work the feeder sizing until the order is automatic, because that is the block where the hardest items live. Motors carry 2 of 24 scored calculations items and 5 of 56 knowledge items, 7 of 80 in all, which is worth a few evenings of preparation on the journeyman paper. Thirty free questions, twenty of them timed will tell you if the order is automatic yet.
Motor arithmetic worked step by step lives on motor calculations, with 25 questions to test it.
Questions people ask
How many motor questions are on the Texas journeyman exam?
The content outline PSI publishes gives motors and generators two of the twenty-four scored items on the journeyman calculations portion. That is the published figure and it is smaller than most candidates expect. The reputation motors have for carrying the calculations belongs to the master exam, where motors and generators is six of thirty scored calculation items and services is eight. Our own bank holds forty-three motor questions, a deliberate overweight, because the method transfers to other areas.
Which current do I use to size motor conductors?
The table current, from the tables the code provides for the motor type and voltage. The nameplate current is what sizes the overload protection. 430.6 makes that split explicit, and six questions in our bank hand you both numbers in the same stem to see which one you reach for. The wrong answer offered on those items is the number you get from using the other current, which is why it looks reasonable when you land on it.
How do I size a feeder for several motors?
The largest motor at 125 percent of its full load current, every other motor at its full load current, and the sum of those is the feeder load. The execution errors are applying 125 percent to all of the motors or to none of them, and both of those results are usually offered as answer choices. Five of the nine hardest items in this area are feeder problems, so the order is worth drilling until it runs without thinking about it.
Does the Texas 210.8(F) HVAC exception still apply after September 2026?
The national 2026 text expired it on 1 September 2026 through a sentence inside the exception. 16 TAC 73.100(b) adopts that exception into Texas with the expiry sentence removed, so in Texas it continues. You are examined on the code as Texas adopted it. This is the clearest live case of the adopted state edition differing from the national one.
Are transformer calculations on the journeyman exam?
They appear, and they are lighter than motors. Fourteen questions across our whole bank mention a transformer and they sit in four different subject areas, with only two in theory and six in grounding. Primary and secondary protection is at 450.5 in the 2026 edition, having moved from 450.3. For a journeyman candidate the practical target is knowing where the section is and how the primary and secondary sides are treated separately, which is a couple of hours of work.